Siemens 6EP3437-8SB00-0AY0
SITOP PSU8200 24 V/40 A stabilized power supply input: 400-500 V 3 AC output: 24 V DC/40 A *Ex approval no longer available*
Data sheet 6EP3437-8SB00-0AY0
SITOP PSU8200/3AC/24VDC/40A
SITOP PSU8200 24 V/40 A stabilized power supply input: 400-500 V 3 AC output:
24 V DC/40 A *Ex approval no longer available*
Input
type of the power supply network 3-phase AC
supply voltage at AC
● minimum rated value 400 V
● maximum rated value 500 V
● initial value 320 V
● full-scale value 575 V
design of input wide range input Yes
operating condition of the mains buffering at Vin = 400 V
buffering time for rated value of the output current in the event of
power failure minimum
10 ms
operating condition of the mains buffering at Vin = 400 V
line frequency
● 1 rated value 50 Hz
● 2 rated value 60 Hz
line frequency 45 ... 65 Hz
input current
● at rated input voltage 400 V 2.1 A
● at rated input voltage 500 V 1.7 A
current limitation of inrush current at 25 °C maximum 13 A
I2t value maximum 2.24 A²·s
fuse protection type none
● in the feeder Required: 3-pole connected miniature circuit breaker 10 ... 16 A characteristic C
or circuit breaker 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489)
Output
voltage curve at output Controlled, isolated DC voltage
output voltage at DC rated value 24 V
output voltage
● at output 1 at DC rated value 24 V
relative overall tolerance of the voltage 3 %
relative control precision of the output voltage
● on slow fluctuation of input voltage 0.1 %
● on slow fluctuation of ohm loading 0.2 %
residual ripple
● maximum 100 mV
voltage peak
● maximum 240 mV
adjustable output voltage 24 ... 28 V
product function output voltage adjustable Yes
type of output voltage setting via potentiometer; max. 960 W
display version for normal operation Green LED for 24 V OK
6EP34378SB000AY0
Page 1/3 1/8/2024 Subject to change without notice
© Copyright Siemens
type of signal at output Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK"
behavior of the output voltage when switching on minimal overshooting (< 2 %)
response delay maximum 0.1 s
voltage increase time of the output voltage
● maximum 100 ms
output current
● rated value 40 A
● rated range 0 ... 40 A; +60 ... +70 °C: Derating 4%/K
supplied active power typical 960 W
short-term overload current
● at short-circuit during operation typical 120 A
duration of overloading capability for excess current
● at short-circuit during operation 25 ms
constant overload current
● on short-circuiting during the start-up typical 44 A
product feature
● bridging of equipment Yes; switchable characteristic
number of parallel-switched equipment resources for increasing
the power
2
Efficiency
efficiency in percent 94 %
power loss [W]
● at rated output voltage for rated value of the output
current typical
66 W
● during no-load operation maximum 4 W
Closed-loop control
relative control precision of the output voltage with rapid
fluctuation of the input voltage by +/- 15% typical
1 %
relative control precision of the output voltage load step of
resistive load 50/100/50 % typical
3 %
setting time
● maximum 10 ms
Protection and monitoring
design of the overvoltage protection < 31.8 V
● typical 44 A
property of the output short-circuit proof Yes
design of short-circuit protection Alternatively, constant current characteristic approx. 44 A or latching shutdown
enduring short circuit current RMS value
● typical 50 A
overcurrent overload capability in normal operation overload capability 150 % Iout rated up to 5 s/min
display version for overload and short circuit LED yellow for "overload", LED red for "latching shutdown"
Safety
galvanic isolation between input and output Yes
galvanic isolation Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178
operating resource protection class Class I
leakage current
● maximum 1 mA
● typical 0.6 mA
protection class IP IP20
Approvals
certificate of suitability
● CE marking Yes
● UL approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus
(CSA C22.2 No. 60950-1, UL 60950-1)
● CSA approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus
(CSA C22.2 No. 60950-1, UL 60950-1)
● NEC Class 2 No
● EAC approval Yes
● Regulatory Compliance Mark (RCM) Yes
type of certification
● BIS Yes; R-41183539
● CB-certificate Yes
6EP34378SB000AY0
Page 2/3 1/8/2024 Subject to change without notice
© Copyright Siemens
certificate of suitability
● IECEx No
● ATEX No
● ULhazloc approval No
● cCSAus, Class 1, Division 2 No
● FM registration No
certificate of suitability shipbuilding approval Yes
Marine classification association
● American Bureau of Shipping Europe Ltd. (ABS) Yes
● French marine classification society (BV) No
● Lloyds Register of Shipping (LRS) No
EMC
standard
● for emitted interference EN 55022 Class B
● for mains harmonics limitation EN 61000-3-2
● for interference immunity EN 61000-6-2
environmental conditions
ambient temperature
● during operation -25 ... +70 °C; With natural convection
● during transport -40 ... +85 °C
● during storage -40 ... +85 °C
environmental category according to IEC 60721 Climate class 3K3, 5 … 95% no condensation
Mechanics
type of electrical connection screw-type terminals
● at input L1, L2, L3, PE: 1 screw terminal each for 0.5 ... 4 mm² single-core/finely
stranded
● at output +: 2 screw terminals each for 0.5 ... 16 mm²; -: 3 screw terminals each for 0.5 ...
16 mm²
● for auxiliary contacts 13, 14 (alarm signal), 15, 16 (Remote): 1 screw terminal each for 0.05 ... 2.5
mm²
width of the enclosure 135 mm
height of the enclosure 145 mm
depth of the enclosure 150 mm
required spacing
● top 40 mm
● bottom 40 mm
● left 0 mm
● right 0 mm
net weight 3.3 kg
product feature of the enclosure housing can be lined up Yes
fastening method Snaps onto DIN rail EN 60715 35x15
electrical accessories Buffer module
mechanical accessories Device identification label 20 mm × 7 mm, TI-grey 3RT2900-1SB20
MTBF at 40 °C 517 015 h
other information Specifications at rated input voltage and ambient temperature +25 °C (unless
otherwise specified)
6EP34378SB000AY0
Page 3/3 1/8/2024 Subject to change without notice
© Copyright Siemens